1. Singapore
  2. All 3M Products
  3. Electrical
  4. Power Cable Connectors
  5. Power Cable Terminations
  6. 3M™ Cold Shrink QT-III Silicone Rubber Termination Kit, 2-Skirt, 7622-S-2(L), Tape, Wire and UniShield®, 15 kV, 0.69-1.22 in (17,5-31,0 mm) Cable Insul. O.D., 3 terminations/kit

3M™ Cold Shrink QT-III Silicone Rubber Termination Kit, 2-Skirt, 7622-S-2(L), Tape, Wire and UniShield®, 15 kV, 0.69-1.22 in (17,5-31,0 mm) Cable Insul. O.D., 3 terminations/kit

Part Number 7622-S-2(L)3M ID 80611613821
  • One-piece cold shrink termination with integrated environmental top-seal.
  • Integrated High-K stress control mastic manages electric field stress and eliminates field applied silicone grease
  • Suitable for outdoor applications
  • Silicone rubber insulation offers track-resistance, hydrophobic action and provides constant radial pressure
 More
View all details
View Legal Disclaimer
Details
  • One-piece cold shrink termination with integrated environmental top-seal.
  • Integrated High-K stress control mastic manages electric field stress and eliminates field applied silicone grease
  • Suitable for outdoor applications
  • Silicone rubber insulation offers track-resistance, hydrophobic action and provides constant radial pressure
  • Comes with sufficient materials to make 3-single phase terminations
  • Voltage rating per class of termination family: 5/8 kV:95 kV BIL, 15 kV;110 kV BIL, 25 kV;150 kV BIL and 35 kV;200kV BIL
  • Meets IEEE Standard 48 Class 1 for outdoor, weather-exposed applications

3M™ Cold Shrink QT-III 7620-S, 7680-S & 7690-S Series Termination Kits include three 1-piece, skirted terminations. Each kit has materials to make 3-single phase terminations for tape shield, wire shield and UniShield® power cables.

3M™ Cold Shrink QT-III 7620-S, 7680-S & 7690-S Series Termination Kits are designed for terminating solid dielectric shielded, medium-voltage power cables. The QT-III termination uses a high dielectric constant (High-K) stress control mastic insulated with a molded UV-stable, track-resistant, silicone insulator. The track resistant, hydrophobic propertities of the silicone rubber minimize leakage currents. Meets the requirements of IEEE Standard 48, for Class 1 for outdoor, weather-exposed environments.

Specifications
Brand
3M™
Breakout Boot
No
Cable Insulation Outside Diameter Range (metric)
‎17,5-31,0 mm
Cable Shielding
Tape Shield, UniShield®, Wire Shield
Compatible Lug
QL2-A-2-250
Conductor Size by Voltage
(15 kV) 1/0-4/0 AWG
Conductor Sizes
1/0 AWG, 2/0 AWG, 3/0 AWG, 4/0 AWG
Indoor/Outdoor
Outdoor Skirted
Insulation Level
100%
Insulation Rejacketing
No
Number of Conductors
1
Number of Skirts
2
Product Series
7620-S-2
Product Technology
Cold Shrink
Voltage
15 kV

Legal Disclaimer

Manufacturing Origin: USA

The designation that a product is Manufactured in the USA means the product undergoes substantial transformation in one of our U.S. Manufacturing plants. Some products contain imported components.

Note: 3M products offered on a government contract that require country of origin representation must be certified by 3M Trade Compliance. Contact customer service at 800-245-3573 to request a certificate.