1. All 3M Products

3M™ Cold Shrink Three Conductor Breakout Kit 3C-BOK-3

Part Number 3C-BOK-33M ID 80611610116
  • Designed to allow the use of 3M™ Single Conductor Cable Accessories on 3-core conductor cables
  • Engineered for flexibility of medium-voltage applications
  • 0.7 to 0.92-in O.D. insulation
  • Accommodates 2 AWG to 350 kcmil conductor sizes for 5 to 25/28 kV-rated voltages
 More
Details
  • Designed to allow the use of 3M™ Single Conductor Cable Accessories on 3-core conductor cables
  • Engineered for flexibility of medium-voltage applications
  • 0.7 to 0.92-in O.D. insulation
  • Accommodates 2 AWG to 350 kcmil conductor sizes for 5 to 25/28 kV-rated voltages
  • Includes a cold shrink silicone rubber breakout boot, 3 silicone rubber phase rejacketing sleeves and more

3M™ 3C-BOK Cold Shrink 3-Conductor Breakout Kit allows you to use 1 - (single) conductor accessories on 3- (three) conductor cables. This kit offers greater flexibility for medium-voltage applications, especially in tight spaces. It facilitates quick and easy installation even in confined spaces without the use of special tools.

3M™ 3C-BOK Cold Shrink 3-Conductor Breakout Kit is compatible with conductor cables including 3-conductor type G cables, copper tape shield cables, armored cables and tray cables without armor. The kit contains 1 cold shrink silicone rubber breakout boot, 3 silicone rubber phase rejacketing sleeves, 1 large constant force spring, 1 long tail tinned copper ground braid with solder block, 3 Scotch® Mastic Strip 2230, 1 roll Scotch® Super 33+™ 3/4-in Vinyl Electrical Tape, 1 roll Scotch® Electrical Shielding Tape 24 and an instruction sheet.

Specifications
Brand
3M™
Cable Insulation Outside Diameter Range (metric)
17.8-23.4 mm
Conductor Size by Voltage
(5 kV, 100%) 4/0 AWG–350 kcmil(5 kV, 133%) 3/0 AWG–350 kcmil(8 kV, 100%) 3/0 AWG–350 kcmil(8 kV, 133%) 3/0 AWG–350 kcmil(15 kV, 100%) 1/0–4/0 AWG(15 kV, 133%) 2–3/0 AWG, (25/28 kV, 100%) 1–1/0 AWG
Conductor Size for 15 kV at 100% Insulation
1/0–4/0
Conductor Size for 15 kV at 133% Insulation
2–3/0
Conductor Size for 25/28 kV at 100% Insulation
1–1/0
Conductor Size for 5 kV at 100% Insulation
4/0–350
Conductor Size for 5 kV at 133% Insulation
3/0–350
Conductor Size for 8 kV at 100% Insulation
3/0–350
Conductor Size for 8 kV at 133% Insulation
3/0–350
Maximum Cable Outside Diameter (metric)
78.7 mm
RoHS 2011/65/EU Compliant
Undetermined
RoHS EU Comments
Contact 3M for information