3M™ Cold Shrink QT-III 7600-S-3W Series Termination Kit includes a skirted, 3-phase termination. It ensures a pliable, tight seal for tape shield, wire shield and UniShield® power cables. The conjunction of high dielectric-constant material and sealing compounds allows the termination to withstand voltages of 5 to 35kV.
3M™ Cold Shrink QT-III 7600-S-3W Series Termination Kit is designed for terminating medium voltage, 3/C-shielded cables without ground wires. The track-resistant, silicone rubber construction makes the termination suitable for outdoor applications. The lower surface stress, high dielectric-constant material offers an optimized BIL performance while ensuring a leak-proof, compact fit. The short installed length of the termination makes it ideal for use in compact spaces, comprising motors, starters, switchgear, variable speed drives, transformers and other similar connections. JIS, IEC and AEIC Approved.
Conductor Size Range for
· 5 kV: 500-750 kcmil
· 8 kV: 400-600 kcmil
· 15 kV: 250-450 kcmil
· 25/28 kV: 2/0 AWG-250 kcmil
|
|
---|---|
BIL
|
150 kV
|
Brand
|
3M™
|
Breakout Boot
|
Yes
|
Cable Insulation Outside Diameter Range (metric)
|
23.4-30.0 mm
|
Cable Shielding
|
Tape Shield, UniShield®, Wire Shield
|
Conductor Size by Voltage
|
(5 kV) 500-750 kcmil, (8 kV) 400-600 kcmil, (15 kV) 250-450 kcmil, (25/28 kV) 2/0 AWG-250 kcmil
|
Conductor Sizes
|
2/0 AWG, 250 kcmil, 3/0 AWG, 300 kcmil, 350 kcmil, 4/0 AWG, 400 kcmil, 500 kcmil, 600 kcmil, 700 kcmil, 750 kcmil
|
Indoor/Outdoor
|
Outdoor Skirted
|
Insulation Level
|
100%, 133%
|
Insulation Rejacketing
|
Yes
|
Lug/Stem Connector Included in Kit
|
No
|
Number of Conductors
|
3
|
Number of Skirts
|
4
|
Product Series
|
7600-S-3W
|
Product Technology
|
Cold Shrink
|
RoHS 2011/65/EU Compliant
|
Undetermined
|
RoHS EU Comments
|
Contact 3M for information
|
Voltage
|
15 kV, 25 kV, 5 kV, 8 kV
|
Voltage Application
|
Medium Voltage
|